QUICK ELECTRICAL CALCULATION
MACHINE CURRENT CAPACITY
- Single-phase Motor draws current = 7 A / HP.
- Three-phase Motor draw current = 1.25 A/ HP.
- Full load current of Three-phase Motor= HP x 1.5.
- Full load current of Single-phase Motor= HP x 3.
- No Load current of Three-phase motor = 30% of full load current.
- KW rating of Motor= HP x 0.746.
- Equipments Full load current = 1.39 x KVA (3-Phase 415 V)
- Equipments Full load current = 1.74 x KW (3-Phase 415 V)
ABOUT CT
- Rtaio - I/O Current ratio.
- Burden(VA):- Total burden including pilot wire.(2.5, 5, 10, 15 and 30 VA)
- Class:- Accuracy requird for operation (Metering - 0.2, 0.5, 1 or 3; Protection- 5, 10, 15, 20, 30).
- Nomenclature of CT :- Ratio, VA Burden, Accuracy class, Accuracy limit Factor. Example- 1500/5, 15 VA 5P10 (Ratio- 1500/5, burden- 15 VA, Accuracy class- 5P, ALF - 10)
- As per IEEE metering CT :- 0.3B0.1 rated metering CT is accurate to 0.3%, if the connected secondary burden if impedance does not exceed 0.1 ohms.
- As per IEEE Relay(Protection) CT:- 2.5C100 Relay protection CT is accurate within 2.5% if the secondary burden is less than 1.0 ohm(100volts/100A)
CURRENT CARRYING CAPACITY OF CABLE
- For Copper Wire current capacity (30 sq.mm.) = 6 x wire size in sq.mm. Example:- 4 sq.mm. wire = 6 x 4= 24 A, and 1.5 sq.mm. wire = 6 x 1.5 = 9 A.
- For Copper Cable current capacity = 4 x cable size in sq.mm. Example:- For 10 sq.mm. cable = 4 x 10 = 40 A.
- Nomenclature for cable rating = Uo/U. where, Uo= Phase-ground voltage, U= Phase-Phase voltage, Um= Highest permissible voltage.
INSULATION RESISTANCE
- Insulation resistance value for rotating machine = (KV +1) M-Ohm.
- Insulation resistance value for motor(IS-732) = {(20 x Voltage (L-L))/(1000+(2 x KW)}.
- Insulation resistance value for equipment's (<1 KV)= Minimum 1 M-Ohm.
- Insulation resistance value for equipment's (>1 KV)= KV 1 M-Ohm per 1 KV.
- Insulation resistance value for panel= 2 x KV rating of the Panel.
- Minimum Insulation resistance value (domestic)= 50 M-Ohm/No. of points.(All electrical points with electrical fitting & plugs). Should be less than 0.5 M-Ohm.
- Minimum Insulation resistance value (Commercial)= 100 M-Ohm/No. of points.(All electrical points with electrical fitting & plugs). Should be less than 0.5 M-Ohm.
- Test voltage (AC) for Megger = (2 x Name plate voltage)+1000.
- Test voltage (DC) for Megger = (2 x Name plate voltage).
- Submersible Pump take 0.4 Kwh of extra energy for 1 meter water drop.
BASIC EARTHING RESISTANCE
- Earthing resistance for single pit = 5 M-Ohm, Earthing Grid = 0.5 Ohm.
- As per NEC 1985 Earthing resistance should be <5 Ohm.
- Resistance Between Neutral & Earth <= 1 Ohm.
- Voltage Between Neutral & Earth <= 2 Volt.
- Creepage distance = 18 mm to 22 mm/ KV(for medium air pollution)
- Creepage distance = 25 mm to 33 mm/ KV(for highly air pollution)
Basic Electrical
1HP
|
0.746 KW
|
1KW
|
1.36 HP
|
1WATT
|
0.846 Kla/Hr
|
1WATT
|
3.41 BTU/Hr
|
1KWH
|
3.6 MJ
|
1Cal
|
4.186 J
|
1Tone
|
3530 BTU
|
1Kcal
|
4186 Joul
|
1KWH
|
860 Kcal
|
1Cal
|
4.183 Joule
|
- STAR CONNECTION: - Line voltage = √3*Phase voltage, Line current = Phase current.
- DELTA CONNECTION: - Line voltage = Phase voltage, Line current = √3*Phase current.
Post a Comment
Post a Comment